Medium Voltage Cables 

Medium Voltage Cables to VDE 0276

Three Core 8.7/15KV (Um=17.5KV)
N2XSEY
NA2XSEY
Dimensional Data

Nom. Cross- Section Area

Approx. Conductor Diameter

Nom. Insulation Thickness

Copper Tape Thickness

Copper Wire Screen Area*

Approx. Insulation Diameter

Nom. Sheath Thickness

Approx. Overall Diameter

Approx. Weight

Cu

Al

mm²

mm

mm

mm

mm²

mm

mm

mm

kg / km

kg / km

25

6.05

4.5

0.1

16

16.5

1.7

46

3500

2400

35

7.10

4.5

0.1

16

17.5

1.7

48

3800

2600

50

8.25

4.5

0.1

16

18.7

1.7

51

4400

3000

70

9.90

4.5

0.1

16

20.3

1.8

55

5300

3400

95

11.7

4.5

0.1

16

22.1

1.8

59

6400

4000

120

13.1

4.5

0.1

16

23.5

1.9

62

7400

4500

150

14.3

4.5

0.1

25

24.7

1.9

65

8500

5000

185

16.3

4.5

0.1

25

26.7

2.0

69

10000

5800

240

18.7

4.5

0.1

25

29.1

2.1

75

12200

6800

300

20.9

4.5

0.1

25

31.3

2.1

80

14400

7900

400

23.7

4.5

0.1

35

34.1

2.2

87

17500

9300

*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as standard.

Three Core 8.7/15KV (Um=17.5KV) Galvanized Steel Tape Armoured Cables
N2XSEYBY
NA2XSEYBY
Dimensional Data

Nom. Cross- Section Area

Approx Conductor Diameter

Nom. Insulation Thickness

Copper Tape Thickness

Copper Wire Screen Area*

Approx Insulation Diameter

Nom. Armour Thickness

Nom. Sheath Thickness

Approx. Overall Diameter

Approx. Weight

Cu

Al

mm²

mm

mm

mm

mm²

mm

mm

mm

mm

kg / km

kg / km

25

6.05

4.5

0.1

16

16.5

0.5

2.5

49

3800

3300

35

7.10

4.5

0.1

16

17.5

0.5

2.6

51

4300

3600

50

8.25

4.5

0.1

16

18.7

0.5

2.7

54

4900

4000

70

9.90

4.5

0.1

16

20.3

0.5

2.8

58

5900

4600

95

11.7

4.5

0.1

16

22.1

0.5

2.9

62

7100

5300

120

13.1

4.5

0.1

16

23.5

0.5

3.0

66

8100

5900

150

14.3

4.5

0.1

25

24.7

0.5

3.1

69

9200

6400

185

16.3

4.5

0.1

25

26.7

0.5

3.3

74

10900

7400

240

18.7

4.5

0.1

25

29.1

0.5

3.4

79

13100

8500

300

20.9

4.5

0.1

25

31.3

0.5

3.6

86

16400

10600

400

23.7

4.5

0.1

35

34.1

0.8

3.9

93

19700

12300

*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as standard.

Three Core 8.7/15KV (Um=17.5KV) Galvanized Flat Steel Wire Armoured Cables
N2XSEYFGbY
NA2XSEYFGbY
Dimensional Data

Nom. Cross- Section Area

Approx. Conductor Diameter

Nom. Insulation Thickness

Copper Tape Thickness

Copper Wire Screen Area*

Approx. Insulation Diameter

Nom. Armour Thickness

Nom. Sheath Thickness

Approx. Overall Diameter

Approx. Weight

Cu

Al

mm²

mm

mm

mm

mm²

mm

mm

mm

mm

kg / km

kg / km

25

6.05

4.5

0.1

16

16.5

0.8

2.5

49

3400

3400

35

7.10

4.5

0.1

16

17.5

0.8

2.6

51

4400

3800

50

8.25

4.5

0.1

16

18.7

0.8

2.7

54

5100

4200

70

9.90

4.5

0.1

16

20.3

0.8

2.8

58

6000

4700

95

11.7

4.5

0.1

16

22.1

0.8

2.9

62

7300

5400

120

13.1

4.5

0.1

16

23.5

0.8

3.0

66

8300

6100

150

14.3

4.5

0.1

25

24.7

0.8

3.1

69

9400

6600

185

16.3

4.5

0.1

25

26.7

0.8

3.3

74

11100

7600

240

18.7

4.5

0.1

25

29.1

0.8

3.4

79

13400

8700

300

20.9

4.5

0.1

25

31.3

0.8

3.6

85

15800

10000

400

23.7

4.5

0.1

35

34.1

0.8

3.9

91

19000

11600

*Optional wire screen can be provided in combination of copper tapes. Nominal screen area, as stated in the table, can be supplied as standard.

Electrical Data

 

Nom. Cross- Section Area

 

D C Resistance CU / AL

 

A C Resistance CU / AL

 

Short Circuit Rating of Conductor CU / AL
1 sec

 

Capacitance

 

Charging
Current

Short Circuit Rating of Copper Wire Screen
Per Core
1 sec

Short Circuit Rating of Copper Tape Screen
Per Core
1 sec

 

Reactance

 

Inductance

mm²

µΩm

µΩ/m

kA

pF/m

mA/m

kA

kA

µΩm

nH/m

25

727/1200

927/1538

3.6/2.3

176

0.48

2.6

0.6

132

410

35

524/868

668/1113

5.0/3.2

193

0.53

2.6

0.6

123

390

50

387/641

494/822

6.8/4.4

211

0.58

2.6

0.7

116

370

70

268/443

343/568

9.8/6.3

240

0.65

2.6

0.7

110

350

95

193/320

248/410

13.3/8.5

267

0.73

2.6

0.8

105

330

120

153/253

196/325

17.2/11.0

291

0.79

2.6

0.8

102

320

150

124/206

159/265

21.2/13.5

312

0.85

4.3

0.9

98

310

185

99.1/164

128/211

26.6/17.0

340

0.93

4.3

0.9

95

300

240

75.4/125

98/161

34.9/22.3

375

1.02

4.3

1.0

91

290

300

60.1/100

80/130

43.8/28.0

411

1.12

4.3

1.1

89

280

400

47.0/77.8

64/102

57.3/36.6

454

1.24

5.8

1.2

84

270

Flat Steel wire+Steel Tape Armoured Cables
Three Core 6/10KV (Um=12KV)
Three Core  8.7/15KV (Um=17.5KV)
Three Core 12/20KV (Um=24KV)
Three Core 18/30KV (Um=36KV)
Current Rating for Three Core 1.8/3KV(Um=7.2 )KV to 26/35KV(Um=42KV)
)