Caledonian Cables LTD
Reg No.:4888368
Chinese
 
 
XHHW-2 600V, XLPE Insulated & PVC Sheathed Control Cable
 
Application:
These flame-retardant cable are designed for use in power, control and lighting circuits in a broad range of commercial and industrial applications. Suitable for use in wet or dry locations at 90¡ãC, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 600 volts. May be used in NEC Class I and 11, Division 2 hazardous locations. Recognised for use at 90¡ãC continuous ratings for dry operation, 130¡ãC for emergency overload ratings, and 250¡ãC for short circuit ratings.
 
Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 and UL 44 Paragraph 12.6.
 
Insulation:
Flame-retardant cross-linked polyethylene (FR-XLPE) per ICEA S-73-532 part 3 and UL Standard 44 for Type XHHW-2, VW- 1 conductors.
 
Cabling:
Three or more conductors are assembled round with non hygroscopic fillers as needed.
An optional binder is applied over the assembly. A Nylon rip cord is put under the jacket for ease of stripping.
 
Overall Jacket:
Sunlight-resistant gas/vaportight PVC per UL 1277 table 11-1 & ICEA S-73-532 part 4.
 
Flame Tests:
IEEE 383 70,000 BTUIhr flame test
IEEE 1202 70,000 BTU/hr CSA FT4 flame test
ICEA T-29-520 210,000 BTU/hr flame test
Individual conductors pass the UL VW-1 flame test
 
Color Code:
UL Type TC per Article 336 of the NEC.
Approved for Class 1 circuits per Article 725 of the NEC.
NEMAWC57
 
Insulation Thickness:30 mils
14 AWG (7 Strand)
12 AWG (7 Strand)
10 AWC (18 Strand)
No. of Cores
Nominal Thickness of Jacket (mils/mm)
Nominal Overall Diameter (inches/mm)
Approx.Weight (lbs/1000ft)
Nominal
Thickness
of Jacket
(mils/mm)
Nominal Overall Diameter (inches/mm)
Approx.Weight (lbs/1000ft)
Nominal
Thickness
of Jacket
(mils/mm)
Nominal Overall Diameter (inches/mm)
Approx.Weight (lbs/1000ft)
2
3
4
5
45/1.14
45/1.14
45/1.14
45/1.14
0.37/9.4
0.39/9.9
0.42/10.7
0.46/11.7
65
85
115
135
45/1.14
45/1.14
45/1.14
60/1.52
0.41/10.2
0.43/10.9
0.47/11.9
0.55/13.9
85
120
150
215
45/1.14
45/1.14
60/1.52
60/1.52
0.45/11.4
0.47/11.9
0.56/14.2
0.61/15.5
135
175
225
285
6
7
8
9
60/1.52
60/1.52
60/1.52
60/1.52
0.53/12.5
0.53/13.5
0.56/14.2
0.60/15.2
170
185
215
235
60/1.52
60/1.52
60/1.52
60/1.52
0.58/14.7
0.58/14.7
0.65/16.5
0.68/17.3
235
255
305
340
60/1.52
60/1.52
60/1.52
60/1.52
0.66/16.8
0.66/16,8
0.72/18.3
0.77/19.6
325
355
420
475
10
12
16
19
60/1.52
60/1.52
60/1.52
60/1.52
0.66/16.8
0.68/17.3
0.73/18.5
0.79/20.0
255
295
355
435
60/1.52
60/1.52
80/2.03
80/2.03
0.74/18.8
0.77/19.6
0.88/22.4
0.94/23.9
365
420
540
640
80/2.03
80/2.03
80/2.03
80/2.03
0.88/22.4
0.91/23.1
0.98/24.8
1.06/26.9
555
635
765
935
24
30
37
80/2.03
80/2.03
80/2.03
0.95/24.1
1,02/25.4
1.05/26.7
565
685
815
80/2.03
80/2.03
80/2.03
1.09/27.7
1.16/29.5
1.24/31.5
805
980
1170
80/2.03
80/2.03
80/2.03
1.24/31.5
1.31/33.3
1.41/35.8
1185
1400
1700

 

* Also available in other sizes and other strandings
 
 
 
 

Copyright © 2000 Caledonian Cables Limited. All rights reserved. Date Created: 20th April 2001

Website: www.caledonian-cables.com