Telephone Cables | ||||||||||||
MICA/LSZH Insulated &
LSZH Sheathed Fire Resistant Cables to DIN VDE 0815
JE-H(St)H…Bd FE180 E90 JE-H(St)H…Bd FE180 E90 BMK
Application
The cables are similar in design and application to CW 1600, but with fire barrier tape. They are used for the internal wiring of building when the circuit integrity during fire is paramount. The cable is intended to take the place of LSZH sheathed cables and will withstand similar environments with a similar working life. The cables are intended for use in fire fighting plants with mica tapes, with and without aluminium foil and LSZH outer sheath.
Standards
• EN 50200:2000-02
• EN 50266
• EN 50267
• EN 50268
• BS 6387
• IEC 60331
Construction
Conductors
Solid annealed bare or tinned copper sized 0.8mm as per class 1 of VDE 0295/IEC 60228
Fire Barrier
Mica tape
Insulation
LSZH compound HI1 as per VDE 0207-23
Twisted Pairs
Insulated conductors are twisted into pairs with varying lay length to minimize crosstalk
Cabling Element
Twisted Pairs
Core Assembly
The twisted pairs are stranded to the core in layers
Core Wrapping
One or more non hygroscopic polyester tapes are helically or longitudinally laid with an overlap prior to sheathing
Screen
A laminated Aluminium/Polyester tape in contact with solid copper 0.6mm or 0.8mm drain wire
Inner bedding (for armoured cables)
PE or LSZH compound HM2 as per VDE 0207-24
Armour (for armoured cables)
Either corrugated steel tape armour or galvanized steel wire is applied over an inner polyethylene sheath. For steel tape armour, the 0.15mm thick steel tape is coated with a copolymer and applied with an overlap. For steel wire armour, single layer of galvanized steel wire armour is applied.
Sheath
LSZH compound HM2 as per VDE 0207-24
Ripcord
Nylon ripcord may be placed parallel to the cores to facilitate sheath removal
Drain Wire
A solid tinned earth/continuity wire shall be laid longitudinally for screened cables
Type Codes
JE- |
Fire Alarm Cable |
H |
Halogen Free & Zero Halogen |
Bd |
Unit stranding |
(St) |
Static Shield of aluminium tape |
FE180 |
Insulation Integrity (950°C 180 minutes) |
E90 |
90 minutes Circuit Integrity |
Electrical Properties
Nominal Conductor Diameter |
mm |
0.8 |
Conductor Size |
mm2 |
0.5 |
Ω/km |
34.6 |
|
Ω/km |
73.2 |
|
MΩ.km |
100 |
|
Maximum Average Attenuation @0.8KHz |
dB/km |
1.1 |
Average Mutual Capacitance |
nF/km |
120 |
pF/100m |
200 |
|
Working Voltage |
V |
300 |
Nominal Insulation Thickness |
mm |
0.4 |
Nominal Insulated Conductor Diameter |
mm |
1.6 |
Mechanical and Thermal Properties
Temperature range during operation (fixed state): -30°C – +70°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 10 x Overall Diameter (unarmoured cable);15 x Overall Diameter (armoured cables)
Fire Hazard Performance
1) Minimum Smoke Emission |
IEC 61034, EN 50268 (New: EN 61034), VDE 0482-268 (New: VDE 0482-1034) |
2) Halogen Free |
IEC 60754-1, EN 50267-2-1 |
3) Non corrosive gases |
IEC 60754-2, EN 50267-2-2, VDE 0482-267 |
4) Reduced Fire Propagation |
IEC 60332-3C, EN 50266-2-4, VDE 0482-266-2-4 |
5) Flame Retardancy |
IEC 60332-1, VDE 0482-265-2-1 |
6) Insulation Integrity FE 180 |
DIN VDE 0472-814, IEC 60331, EN 50200, VDE 0482-1 |
7) Circuit Integrity E30 |
DIN 4102-12 |
Colour Code
Quad colour in each bundle:
Pair 1: Blue-Red
Pair 2: Grey-Yellow
Pair 3: Green-Brown
Pair 4: White-Black
The individual bundles are identified by a numbered helix
Dimensions And Weight
VDE CODE: JE-H(St)H…x2x0.8 Bd FE180 E90
Cable Code |
Number |
Nominal |
Nominal Sheath |
Nominal |
Nominal |
0.8mm Conductor, 1.6mm Insulated Wirez |
|||||
TP815JE-H(St)H-Bd-FE180-E90-2P08 |
2 |
0.4 |
1.0 |
12.8 |
177 |
TP815JE-H(St)H-Bd-FE180-E90-4P08 |
4 |
0.4 |
1.0 |
16.3 |
284 |
TP815JE-H(St)H-Bd-FE180-E90-8P08 |
8 |
0.4 |
1.0 |
20.3 |
447 |
TP815JE-H(St)H-Bd-FE180-E90-12P08 |
12 |
0.4 |
1.2 |
23.9 |
615 |
TP815JE-H(St)H-Bd-FE180-E90-16P08 |
16 |
0.4 |
1.2 |
26.6 |
756 |
TP815JE-H(St)H-Bd-FE180-E90-20P08 |
20 |
0.4 |
1.2 |
29.4 |
921 |
TP815JE-H(St)H-Bd-FE180-E90-32P08 |
32 |
0.4 |
1.4 |
30.7 |
1074 |
TP815JE-H(St)H-Bd-FE180-E90-40P08 |
40 |
0.4 |
1.4 |
33.6 |
1278 |
TP815JE-H(St)H-Bd-FE180-E90-52P08 |
52 |
0.4 |
1.6 |
43.7 |
2011 |