These cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency instrumentation, communication, control and alarm systems that need to be operational during a 1100℃hydrocarbon fire.
Electrical Characteristics
Conductors | Circular tinned stranded copper wire to IEC 60228 class 2. |
Insulation | Mica tape + Halogen free EPR compound. |
Twinning | Colour coded cores twisted together. |
Collective Shielding | Pairs/triples are layed up and collectively screened by copper backed polyester tape in contact with a stranded tinned copper drain wire. |
Pairs/triples are numbered with numbered tape or by numbers printed directly on the insulated conductors. | |
Bedding | Halogen free compound. |
Armour | Tinned copper wire braid. |
Outer Sheath1 | Halogen free thermosetting compound, SHF2. |
HC-fire protection | Extruded thermoplastic fire protection compound. |
Taping | Lapped glass fibre tape. |
Outer Sheath2 | Flame retardant halogen-free thermoplastic compound, type SHF1, coloured grey (blue for intrinsically safe). |
Nominal Cross Section Area | mm^2 | 1.5 |
Nominal Conductor Diameter | mm | 1.6 |
Maximum Resistant@20℃ | Ω/km | 12.9 |
Mutual Capacitance | nF/km | 85 |
Nominal Inductance@1KHz | MH/km | 0.667 |
Operating Voltage | V | 250 |
Bending Radius | 20×OD (during installation) |
12×OD (fixed installed) | |
Temperature Range | -20℃ ~ +90℃ |
Construction No. of elements×No. of cores in element×Cross section(mm^2) | Nominal Insulation Thickness (mm) | Nominal Diameter Over Bedding (mm) | Nominal Diameter Over Sheath1 (mm) | Nominal Overall Diameter (mm) | Nominal Weight (kg/km) |
2×2×1.5 | 0.7 | 13.0 | 16.4 | 44.5 | 2400 |
4×2×1.5 | 0.7 | 15.0 | 19.9 | 46.5 | 2650 |
8×2×1.5 | 0.7 | 20.5 | 25.3 | 53.0 | 3570 |
12×2×1.5 | 0.7 | 23.5 | 29.6 | 57.0 | 4160 |