The armoured LSZH sheathed cables are generally used when the risk of mechanical damage isincreased. The galvanized steel wire armour provides excellent protection. Generally, the cables areused within industrial process manufacturing plants for communication, data and voice transmission signals and services. Also used for theinterconnection of electrical equipment and instruments, the LSZH sheath can reduce toxic smoke and fume emission.
Basic design to EN 50288-7
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Sunlight Resistance | UL 1581 section 1200 |
Oil Resistance | ICEA S-73-532** |
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.
300/500V
Conductor Area Size | mm2 | 0.5 | 0.75 | 1.0 | 1.3 | 1.5 | |
Insulation thickness (nominal) | mm | 0.35 | 0.38 | 0.4 | 0.45 | 0.45 | |
Conductor resistance (20°C) | Ω/km | 36.7 | 25 | 18.5 | 14.2 | 12.3 | |
Insulation resistance (20°C) | MΩ.km(Min.) | 5000 | |||||
Mutual Capacitance (1 kHz) | pF/m(Max.) | 115 | |||||
Capacitance unbalance(1 kHz) | pF/500 m (Max.) | 500 | |||||
Inductance | mH/km (Max.) | 1 | |||||
L / R (ratio) (max.) | μH/Ω | 25 | 25 | 25 | 40 | 40 | |
Operating voltage Urms | V | 300 | |||||
Test Voltage | Core to Core | V | 1500 | ||||
Core to Screen | V | 1500 |
Caledonian Cable Code | RE-2Y(St)HSWAH | |||||||
---|---|---|---|---|---|---|---|---|
No. of Pairsx2 xCross Section | Nominal Insulation Thick -ness | Nominal Inner Sheath Thick -ness | Nominal Overall Diameter Over InnerSheath | NominalArmour Wire Diameter | Nominal Outer Sheath Thick -ness | Nominal Overall Diameter | Approx. Weight | |
No.x2xmm2 | mm | mm | mm | mm | mm | mm | kg/km | |
RE-2Y(St)HSWAH 1P0.5 | 1x2x0.50 | 0.35 | 0.8 | 5.2 | 0.9 | 1.3 | 9.6 | 177 |
RE-2Y(St)HSWAH 1P0.75 | 1x2x0.75 | 0.38 | 0.8 | 5.6 | 0.9 | 1.3 | 10.0 | 199 |
RE-2Y(St)HSWAH 1P1.0 | 1x2x1.0 | 0.40 | 0.9 | 6.3 | 0.9 | 1.3 | 10.7 | 219 |
RE-2Y(St)HSWAH 1P1.3 | 1x2x1.3 | 0.45 | 0.9 | 6.8 | 0.9 | 1.3 | 11.2 | 241 |