Quick Contact
These fire resistant cables are used as high-conductivity copper speaker cables.
Conductor : Tinned copper wire.
Insulation : Mica tape+LSZH.
Sheath : LSZH.
Insulation Colour : Black, White.
Circuit Integrity | IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
---|---|
System circuit integrity | DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20- 22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
AWG | 16 | |
---|---|---|
Conductor Construction | 19x0.287 | |
UL Style | 2598 | |
Maximum Conductor Resistance | Ω/km | 15.8 |
Voltage Rating | V | 300 |
Nominal Capacitance Conductor to Conductor | pF/m | 108.3 |
Bending Radius | 19xOverall Diameter | |
Operating Temperature | ℃ | -20~80 |
Ordering Code | No. of Pairs | Insulation Thickness | Sheath Thickness | Overall Diameter |
---|---|---|---|---|
mm | mm | mm | ||
BE118471FR | 1 | 0.584 | 0.81 | 7.46 |