Quick Contact
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Conductor Cross Sectional Area | Reference Method 4 (enclosed in conduit in thermally insulating wall etc) | Reference Method 3 (enclosed in conduit on a wall or in trunking etc) | Reference Method 1 (clipped direct) | Reference Method 11 (on a perforated cable tray, horizontal or vertical) | Reference Method 12 (free air) | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Horizontal flat spaced | Vertical flat spaced | Trefoil | |||||||||
2 cables, single phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single phase a.c. or d.c. flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. or flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single phase a.c. or d.c. or 3 cables three phase | 2 cables, single phase a.c. or d.c. or 3 cables three phase | 3 cables, trefoil 3-phase phase a.c. | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
mm² | A | A | A | A | A | A | A | A | A | A | A |
1.0 | 13 | - | - | - | 15 | - | - | - | - | - | - |
1.5 | 18 | 17 | 22 | 19 | 25 | 23 | - | - | - | - | - |
2.5 | 24 | 23 | 30 | 26 | 34 | 31 | - | - | - | - | - |
Nominal Cross Section Area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. | |||
---|---|---|---|---|---|---|
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1 and 11 (clipped direct or on trays touching) | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1, 11 and 12 | Ref. Methods 1 and 11 | ||
(in trefoil) | (Flat and touching) | |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 |
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
1.0 | 46 | 46 | - | - | - | - |
1.5 | 31 | 31 | 27 | 27 | 27 | 27 |
2.5 | 19 | 19 | 16 | 16 | 16 | 16 |