Quick Contact
Applications
These cables are designed for 400 Hz systems for power supply of aircraft, computer systems and radar stations, suitable for laying in earth, in water, outdoors, indoors and in cable ducts.
Standards
VDE 0295
Construction
Conductor: Stranded copper conductor, Class 5/Class 6 to VDE 0295/IEC 60228.
Insulation: XLEPR.
Control Core: 1mm² stranded copper conductor with polyolefin insulation.
Sheath: PUR.
Technical Data
Rated Voltage Uo/U (Um) | 600/1000V |
Operating Temperatures | -40℃~+90℃ |
Minimum Bending Radius | static: 4×OD; dynamic: 5×OD |
Halogen Free | Yes |
No Corrosive & Toxic Gases | Yes |
Flame Retardant | Yes |
Abrasion Resistant | Yes |
UV Resistant | Yes |
Oil Resistant | Yes |
Dimensions and Weight
Construction | Nominal Diameter of Single Core |
Nominal Overall Diameter | Nominal Weight |
---|---|---|---|
No. ×mm² | mm | mm | kg/km |
4×(1×35+4×1) | 13.7 | 33.0 | 2600 |
4×(1×50+4×1) | 18.2 | 44.0 | 3900 |
4×(1×70+4×1) | 21.2 | 51.3 | 4300 |
4×(1×120+4×1) | 23.2 | 56.0 | 7400 |