Airport Cable | |||
600/1000V XLPE Insulated, PVC Sheathed, Armoured Power Cables (Single Core)
FGD300 1RVMV-R (CU/XLPE/PVC/AWA/PVC 600/1000V Class 2)
APPLICATION
The cables is mainly used in power stations, mass transit underground passenger systems,
airports, petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design to BS 5467
FIRE PERFORMANCE
FlameRetardance (SingleVerticalWireTest)** |
EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** |
EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the
PVC compound and the cable design.
VOLTAGE RATING
600/1000V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Inner sheath : PVC Compound
Armouring : Aluminium Wire
Outer Sheath : Thermoplastic PVC compound .
COLOUR CODE
Insulation Colour: Natural
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature Range During Operation: -40°C ~ 70°C
Temperature Range during Installation : -5°C ~ 50°C
Minimum Bending Radius: 8 x OD
Electrical PROPERTIES
DielectricTest: |
3500 Vr.m.s.x 5’(core/core) |
Insulation Resistance |
500 MΩ x km ( at 20°C ) |
ShortcircuitTemperature |
250°C ( up to5secs) |
CONSTRUCTION PARAMETERS
Cable |
Conductor |
Diameter |
Armour Wire Diameter |
Nominal |
Approx. Weight |
|
No. of CoreX CrossSection |
No./Nominal |
|||||
|
mm2 |
No./mm |
mm |
mm |
mm |
kg/km |
FFGD3001RVMV-R 1G70 |
1x70 |
19/2.14 |
15.4 |
1.25 |
21.5 |
960 |
FFGD3001RVMV-R 1G95 |
1x95 |
19/2.52 |
17.3 |
1.25 |
23.4 |
1240 |
FFGD3001RVMV-R 1G120 |
1x120 |
37/2.03 |
19.1 |
1.6 |
25.9 |
1650 |
FFGD3001RVMV-R 1G150 |
1x150 |
37/2.25 |
21.1 |
1.6 |
27.9 |
1970 |
FFGD3001RVMV-R 1G185 |
1x185 |
37/2.52 |
23.2 |
1.6 |
30.1 |
2390 |
FFGD3001RVMV-R 1G240 |
1x240 |
61/2.25 |
26.2 |
1.6 |
33.2 |
3040 |
FFGD3001RVMV-R 1G300 |
1x300 |
61/2.52 |
28.8 |
1.6 |
35.8 |
3790 |
FFGD3001RVMV-R 1G400 |
1x400 |
61/2.85 |
32.7 |
2.0 |
40.9 |
4790 |
FFGD3001RVMV-R 1G500 |
1x500 |
61/3.20 |
36.2 |
2.0 |
44.6 |
5880 |
FFGD3001RVMV-R 1G630 |
1x630 |
127/2.52 |
40.6 |
2.0 |
49.2 |
7400 |
FFGD3001RVMV-R 1G800 |
1x800 |
127/2.85 |
45.7 |
2.5 |
55.7 |
9500 |
FFGD3001RVMV-R 1G1000 |
1x1000 |
127/3.20 |
50.6 |
2.5 |
61.0 |
11750 |
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor |
Reference Method1(clipped direct) |
Reference horizontalcabletrayor |
Reference |
Insingle- |
Laiddirectin |
||||
|
2 cables, single- phase a.c.ord.c. |
3 or 4cables, 3-phasea.c. |
2 cables, single- phase a.c.ord.c. |
3 or 4cables, 3-phasea.c. |
3cables 3-phase a.c.trefoiltouching |
2 cables, single- phase a.c.ord.c. |
3 or 4cables, 3-phasea.c. |
2 cables, single- phase a.c.ord.c. |
3 or 4cables, 3-phasea.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
A |
70 |
303 |
277 |
322 |
293 |
285 |
310 |
280 |
340 |
290 |
95 |
367 |
333 |
389 |
352 |
346 |
365 |
330 |
405 |
345 |
120 |
425 |
383 |
449 |
405 |
402 |
410 |
370 |
460 |
389 |
150 |
488 |
437 |
516 |
462 |
463 |
445 |
405 |
510 |
435 |
185 |
557 |
496 |
587 |
524 |
529 |
485 |
440 |
580 |
490 |
240 |
656 |
579 |
689 |
612 |
625 |
550 |
500 |
670 |
560 |
300 |
755 |
662 |
792 |
700 |
720 |
610 |
550 |
750 |
630 |
400 |
853 |
717 |
899 |
767 |
815 |
640 |
580 |
830 |
700 |
500 |
962 |
791 |
1016 |
851 |
918 |
690 |
620 |
910 |
770 |
630 |
1082 |
861 |
1146 |
935 |
1027 |
750 |
670 |
1000 |
840 |
800 |
1170 |
904 |
1246 |
987 |
1119 |
828 |
735 |
1117 |
931 |
1000 |
1261 |
961 |
1345 |
1055 |
1214 |
919 |
811 |
1254 |
1038 |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectionalarea |
2 cablesd.c. |
2cables single-phasea.c. |
3 or 4 cables three-phase a.c. |
2 cables |
3 or 4 cables,3-phase a.c.touching |
|||||||||
Reference Method 1 & 11 (touching) |
Reference Method1, 11 & 12 (intrefoiltouching) |
Reference Method 1 &11(Flattouching) |
In ducts |
In ground |
In ducts |
In ground |
||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
||||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
||||||
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
|
|
|
|
70 |
0.67 |
0.68 |
0.20 |
0.71 |
0.59 |
0.17 |
0.62 |
0.6 |
0.25 |
0.65 |
0.80 |
0.70 |
0.70 |
0.61 |
95 |
0.49 |
0.51 |
0.195 |
0.55 |
0.44 |
0.17 |
0.47 |
0.46 |
0.24 |
0.52 |
0.65 |
0.53 |
0.56 |
0.46 |
120 |
0.39 |
0.41 |
0.190 |
0.45 |
0.35 |
0.165 |
0.39 |
0.38 |
0.24 |
0.44 |
0.55 |
0.43 |
0.48 |
0.37 |
150 |
0.31 |
0.33 |
0.185 |
0.38 |
0.29 |
0.160 |
0.33 |
0.31 |
0.23 |
0.39 |
0.50 |
0.37 |
0.43 |
0.32 |
185 |
0.25 |
0.27 |
0.185 |
0.33 |
0.23 |
0.160 |
0.28 |
0.26 |
0.23 |
0.34 |
0.45 |
0.31 |
0.39 |
0.27 |
240 |
0.195 |
0.21 |
0.180 |
0.28 |
0.18 |
0.155 |
0.24 |
0.21 |
0.22 |
0.30 |
0.40 |
0.26 |
0.35 |
0.23 |
300 |
0.155 |
0.17 |
0.175 |
0.25 |
0.145 |
0.150 |
0.21 |
0.17 |
0.22 |
0.28 |
0.37 |
0.24 |
0.32 |
0.21 |
400 |
0.115 |
0.145 |
0.170 |
0.22 |
0.125 |
0.150 |
0.195 |
0.160 |
0.21 |
0.27 |
0.35 |
0.21 |
0.30 |
0.19 |
500 |
0.093 |
0.125 |
0.170 |
0.21 |
0.105 |
0.145 |
0.180 |
0.145 |
0.20 |
0.25 |
0.33 |
0.20 |
0.28 |
0.18 |
630 |
0.073 |
0.105 |
0.165 |
0.195 |
0.092 |
0.145 |
0.170 |
0.135 |
0.195 |
0.24 |
0.30 |
0.19 |
0.26 |
0.17 |
800 |
0.056 |
0.090 |
0.160 |
0.190 |
0.086 |
0.140 |
0.165 |
0.130 |
0.180 |
0.23 |
0.28 |
0.18 |
0.24 |
0.16 |
1000 |
0.045 |
0.092 |
0.155 |
0.180 |
0.080 |
0.135 |
0.155 |
0.125 |
0.170 |
0.21 |
0.26 |
0.17 |
0.22 |
0.15 |
r = conductor resistance at operating temperature
x = reactance
z = impedance