Airport Cable  

   FFX300 1mRZ1MZ1-R (CU/MGT+XLPE/LSZH/AWA/LSZH 600/1000V Single Core)

600/1000V Mica/XLPE Insulated, LSZH Sheathed, Armoured Power Cables (Single Core)

APPLICATION
This cable is designed for areas where the integrity of the electrical properties circuit is critical in
maintaining power supply. Applications can be found in emergency lightings, control and power
circuits, power stations, fire alarm systems, underground tunnels, communications systems,
sewage treatment plants, lifts, escalators, and high-rise buildings.
STANDARDS
Basic design to BS 7846
FIRE PERFORMANCE

 

Circuit Integrity

IEC60331-21;BS6387 CWZ;DINVDE0472-814(FE180);

CEI20-36/2-1; SS229-1;NBNC30-004 (cat.F3);NF C32-070-2.3(CR1)

SystemCircuitIntegrity

DIN4102-12, E30depending on lay system

 

Flame Retardance (SingleVerticalWireTest)

EN60332-1-2; IEC60332-1-2; BSEN60332-1-2;VDE0482-332-1 ; NBNC30-004 (cat.F1);

NF C32-070-2.1(C2); CEI 20-35/1-2; EN50265-2-1*;DIN VDE 0482-265-2-1*

Reduced FirePropagation(Vertically-mountedbundledwires

&cabletest)

EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBNC30-004(cat.F2);NFC32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen Free

IEC60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI20-37/2-1;BS6425-1*

NoCorrosive GasEmission

IEC60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI20-37/2-2;BS6425-2*

MinimumSmokeEmission

IEC61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI20-37/3-1&2; EN50268-1&2*;BS 7622-1&2*

NoToxic Gases

NES02-713;NF C 20-454

Note: Asterisk * denotes superseded standard.

VOLTAGE RATING
600/1000 V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC 60228 class 2.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound
Inner Sheath :Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
Armouring : Aluminum wire armour
Outer Sheath:Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
COLOUR CODE
Insulation Colour : Natural
Sheath Colour: Black (other colors upon request)
Physical AND THERMAL PROPERTIES
Temperature Range During Operation: -30°C ~ 90°C
Temperature Range during Installation : -5°C ~ 50°C
Minimum Bending Radius: 8 x OD
Electrical PROPERTIES

 

DielectricTest:

 

3500 Vr.m.s.x 5’(core/core)

Insulation Resistance

1000 MΩ x km ( at20°C )

ShortCircuitTemperature

250°C ( up to5secs)

CONSTRUCTION PARAMETERS

 

 

 

Cable
Code

Conductor

 

 

Approx. Overall Diameter

 

 

 

Approx. Weight

No.of
Core

×Cross Section

No./

Nominal
Diameter
of
Strands

 

Dia.of
Conductor

 

Nominal
Insulation Thickness

 

mm2

No./mm

mm

mm

mm

kg/km

FFX300 1mRZ1MZ1-R1G1.5

1×1.5

7/0.53

1.59

0.7

-

-

FFX300 1mRZ1MZ1-R1G2.5

1×2.5

7/0.67

2.01

0.7

-

-

FFX300 1mRZ1MZ1-R1G4

1×4

7/0.85

2.55

0.7

-

-

FFX300 1mRZ1MZ1-R1G6

1×6

7/1.04

3.12

0.7

-

-

FFX300 1mRZ1MZ1-R1G10

1×10

7/1.35

4.05

0.7

-

-

FFX300 1mRZ1MZ1-R1G16

1×16

7/1.70

5.1

0.7

-

-

FFX300 1mRZ1MZ1-R1G25

1×25

7/2.14

6.42

0.9

-

-

FFX300 1mRZ1MZ1-R1G35

1×35

19/1.53

7.65

0.9

-

-

FFX300 1mRZ1MZ1-R1G50

1×50

19/1.78

8.9

1

18.5

780

FFX300 1mRZ1MZ1-R1G70

1×70

19/2.14

10.7

1.1

20.5

1010

FFX300 1mRZ1MZ1-R1G95

1×95

19/2.52

12.6

1.1

23

1320

FFX300 1mRZ1MZ1-R1G120

1×120

37/2.03

14.21

1.2

24.5

1610

FFX300 1mRZ1MZ1-R1G150

1×150

37/2.25

15.75

1.4

27

2010

FFX300 1mRZ1MZ1-R1G185

1×185

37.2.52

17.64

1.6

29.5

2440

FFX300 1mRZ1MZ1-R1G240

1×240

61/2.25

20.25

1.7

34.5

3060

FFX300 1mRZ1MZ1-R1G300

1×300

61/2.52

22.68

1.8

36.9

3690

FFX300 1mRZ1MZ1-R1G400

1×400

65/2.85

25.65

2

41.5

4780

FFX300 1mRZ1MZ1-R1G500

1×500

61/3.20

28.8

2.2

45.5

5970

FFX300 1mRZ1MZ1-R1G630

1×630

127/2.52

32.76

2.4

50.5

7530

FFX300 1mRZ1MZ1-R1G800

1×800

127/2.85

37.05

2.6

56.8

9680

FFX300 1mRZ1MZ1-R1G1000

1×1000

127/3.20

41.6

2.8

61.5

11980

ElectricAl PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

 

 

 

 

 

Nominal
Cross
Section Area

 Reference
Method1
(clipped
direct)

 Reference
Method11(on

perforated
cabletray)

 

Reference
Method 12(free air)

 Insingle-
wayducts

 Laiddirectin
ground

 2cables singlephase a.c.

or d.c.flat and touching

 3 or 4cables 3-phase

a.c. flat

andtouching

 2cables singlephase a.c.
or d.c.flat and touching

 3 or 4cables 3-phase
a.c. flat
and
touching

 3cables
3-phase

a.c.trefoil
touching

 2cables singlephase a.c.
ord.c. ducts
touching

 3cables
3-phase
a.c.trefoil
touching

 2cables singlephase a.c.
ord.c.
touching

 3cables
3-phase

a.c.trefoil
touching

1

2

3

4

5

6

7

8

9

10

mm2

A

A

A

A

A

A

A

A

A

50

237

220

253

232

222

255

235

275

235

70

303

277

322

293

285

310

280

340

290

95

367

333

389

352

346

365

330

405

345

120

425

383

449

405

402

410

370

460

389

150

488

437

516

462

463

445

405

510

435

185

557

496

587

524

529

485

440

580

490

240

656

579

689

612

625

550

500

670

560

300

755

662

792

700

720

610

550

750

630

400

853

717

899

767

815

640

580

830

700

500

962

791

1016

851

918

690

620

910

770

630

1082

861

1146

935

1027

750

670

1000

840

800

1170

904

1246

987

1119

828

735

1117

931

1000

1261

961

1345

1055

1214

919

811

1254

1038

Voltage Drop (Per Amp Per Meter)

Nominal

Cross
Section Area

 

 

 

 

1

2

cables d.c.

 

 

 

 

2

2cables
single- phase

a.c.

 

3or 4cables
three-
phasea.c.

2cables single
phase a.c.

3 or 4cables,3-phasea.c.
touching

Reference Method1&

11(touching)

Reference
Method

1,11

& 12 (intrefoiltouching)

Reference
Method1&11
(Flat touching)

 

Inducts

 

6

 

Inground

 

7

 

Inducts

 

8

 

Inground

 

9

3

4

5

mm2

mV/A/m

 

mV/A/m

 

mV/A/m

 

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

 

 

r

x

z

r

x

z

r

x

z

 

 

 

 

50

0.98

0.99

0.21

1

0.86

0.18

0.87

0.84

0.25

0.88

1.1

0.99

0.93

0.86

70

0.67

0.68

0.2

0.71

0.59

0.17

0.62

0.6

0.25

0.65

0.8

0.7

0.7

0.61

95

0.49

0.51

0.195

0.55

0.44

0.17

0.47

0.46

0.24

0.52

0.65

0.53

0.56

0.46

120

0.39

0.41

0.19

0.45

0.35

0.165

0.39

0.38

0.24

0.44

0.55

0.43

0.48

0.37

150

0.31

0.33

0.185

0.38

0.29

0.16

0.33

0.31

0.23

0.39

0.5

0.37

0.43

0.32

185

0.25

0.27

0.185

0.33

0.23

0.16

0.28

0.26

0.23

0.34

0.45

0.31

0.39

0.27

240

0.195

0.21

0.18

0.28

0.18

0.155

0.24

0.21

0.22

0.3

0.4

0.26

0.35

0.23

300

0.155

0.17

0.175

0.25

0.145

0.15

0.21

0.17

0.22

0.28

0.37

0.24

0.32

0.21

400

0.115

0.145

0.17

0.22

0.125

0.15

0.195

0.16

0.21

0.27

0.35

0.21

0.3

0.19

500

0.093

0.125

0.17

0.21

0.105

0.145

0.18

0.145

0.2

0.25

0.33

0.2

0.28

0.18

630

0.073

0.105

0.165

0.195

0.092

0.145

0.17

0.135

0.195

0.24

0.3

0.19

0.26

0.17

800

0.056

0.09

0.16

0.19

0.086

0.14

0.165

0.13

0.18

0.23

0.28

0.18

0.24

0.16

1000

0.045

0.092

0.155

0.18

0.08

0.135

0.155

0.125

0.17

0.21

0.26

0.17

0.22

0.15

Note: r = conductor resistance at operating temperature
x = reactance
z = impedance