Industrial Cables  

Australian Standard (Medium Voltage)

3.8/6.6kV Three Core Individual Screened & PVC/SWA/PVC Sheathed (Al Conductor)

Application

3.8/6.6kV Three Core Individual Screened & PVC/SWA/PVC Sheathed (Al Conductor)

3.8/6.6kV Three Core Individual Screened & PVC/SWA/PVC Sheathed (Al Conductor) cables are designed to be used for the supply of electrical energy in fixed applications up to the rated voltages at a nominal power frequency between 49Hz and 61Hz.,3.8/6.6kV Three Core Individual Screened & PVC/SWA/PVC Sheathed (Al Conductor) cables are suitable for use in distribution installation, electrical power station , they are applied for installation, outdoors, underground where subject to mechanical damage.

Standard

AS/NZS 1429.1

Cable Construction

CONDUCTOR: Plain circular compacted aluminium to AS/NZS1125 Maximum Continuous Operating Temperature: 90°C
CONDUCTOR SCREEN: Extruded semi-conducting compound, bonded to the insulation and applied in the same operation as the insulation

INSULATION: Cross Linked Polyethylene (XLPE) – standard Ethylene Propylene Rubber (EPR) – alternative

INSULATION SCREEN: Extruded semi-conducting compound

METALLIC SCREEN: Plain annealed copper wire: 10kA for nominal 1 second(HEAVY DUTY)

BEDDING: PVC

ARMOURING: Galvanised steel wires

SHEATH: Black 5V-90 polyvinyl chloride (PVC) – standard

Orange 5V-90 PVC inner plus black high density polyethylene (HDPE) outer – alternative Low smoke zero halogen (LSOH) – alternative

Technical Characteristics

Nominal conductor area Maximum Conductor DC resistance at 20°C Cond. AC resistance at 50Hz and 90°C Inductive reactance at 50Hz Insulation resistance at 20°C Conductor to screen capacitance Charg
ing current per phase
Diel
ectric loss per phrase
Maxi
mum diael
ectric stress
Scree
nDC resist
ance at 20°C
ArmourDC resistance at 20°C Zero sequ
ence
resis
tance at 20°C
Zero seq. react.
at 50Hz
mm2 Ohm/km Ohm/km Ohm/km MegOhm. km µF x km A x
km
W x km kV x mm Ohm
/km
Ohm/km Ohm/km Ohm/km

35

0.868

1.11

0.12

8700

0.278

0.332

5.04

1.92

0.761

0.643

1.91

0.0709

50

0.641

0.822

0.115

7800

0.309

0.369

5.61

1.87

0.559

0.616

1.52

0.0658

70

0.443

0.569

0.106

6800

0.353

0.422

6.41

1.82

0.393

0.559

1.14

0.0574

95

0.32

0.41

0.101

6000

0.4

0.478

7.26

1.77

0.295

0.521

0.884

0.0528

120

0.253

0.325

0.0976

5500

0.439

0.524

7.96

1.74

0.265

0.487

0.769

0.0497

150

0.206

0.265

0.0948

5100

0.477

0.569

8.66

1.72

0.266

0.465

0.714

0.0472

185

0.164

0.211

0.0923

4700

0.518

0.618

9.4

1.7

0.265

0.438

0.66

0.0449

240

0.125

0.162

0.0896

4300

0.561

0.67

10.2

1.62

0.265

0.312

0.556

0.0424

300

0.1

0.13

0.0885

4100

0.582

0.695

10.6

1.5

0.265

0.288

0.515

0.0415

400

0.0778

0.102

0.0857

3900

0.613

0.731

11.1

1.39

0.265

0.261

0.473

0.039

Cable Parameter

Sectional Area of Conductor Nom. Conductor Diameter Nom. Insulation Thickness Nom. Diamete Over insulation Screen Area on cores No. and Diamter of Screened Wires Nom. Diamete Over Screened Wires Nom. Diamete Over Bedding Nom. Diamete of Armour Nom. Diamete Over Armour Nom. Overall Diameter Approx. mass
mm2 mm mm mm mm2 no x mm mm mm mm mm mm kg/100m
35 6.9 2.5 13 23.8 14 x 0.85 16.3 38.6 2.5 43.6 48.6 370
50 8.1 2.5 14.2 32.3 19 x 0.85 17.5 41.1 2.5 46.1 51.5 410
70 9.6 2.5 15.8 46 27 x 0.85 19.1 44.7 2.5 49.7 55.3 480
95 11.4 2.5 17.5 61.3 36 x 0.85 20.8 48.6 2.5 53.6 59.4 555
120 12.8 2.5 18.9 68.1 40 x 0.85 22.2 51.6 2.5 56.6 62.6 615
150 14.2 2.5 20.3 68.1 40 x 0.85 23.6 54.9 2.5 59.9 66.1 665
185 15.7 2.5 21.8 68.1 40 x 0.85 25.1 58.3 2.5 63.3 69.7 735
240 18 2.6 24.3 68.1 40 x 0.85 27.6 63.9 3.15 70.2 77.3 940
300 20.1 2.8 27 68.1 40 x 0.85 30.3 70 3.15 76.3 83.7 1070
400 23 3 30.3 68.1 40 x 0.85 33.6 77.2 3.15 83.5 91.4 1240