Control Cables | |||
VDE Standard Control Cable
CY PVC/PVC /TCWB/ PVC Control Cable
Application:
For use as a measuring, control and signal cable for the machine tool industry, plant construction, heating and air conditioning etc, and are particularly suitable between fixed and mobile equipment. The cable is well protected against electrical interference by the narrow weave tinned copper-wire braid screen, which ensures the undisturbed transmission of pulses and signals in electronic fields.
* Note: should not be used in any installations where the cable is subjected to repetitive flexing.
Standards: Generally BS6500 VDE0250
Conductor: Class 5 annealed copper conductors to BS6360 / VDE0295
Insulation: PVC
Bedding: PVC
Braiding: Tinned Copper Wire Braid (TCWB)
Sheath: PVC (Type TM2 to BS7655)
Voltage Rating: 300/500V
Temperature rating:
Flexing -15 to +70°C
Static -35 to +70°C
Minimum bending radius: 6 x overall diameter
Core identification: Black with White numbers. (3 core and above to include Green/Yellow)
Coloured cores available on request
Current Carrying Capacity (amperes)
Nominal Cross Sectional Area |
Single Phase AC or DC |
Three Phase AC |
mm2 |
Amps |
Amps |
0.5 |
3 |
3 |
0.8 |
6 |
6 |
1.0 |
10 |
10 |
1.5 |
16 |
16 |
2.5 |
25 |
20 |
4.0 |
32 |
25 |
6.0 |
51 |
43 |
10.0 |
70 |
60 |
16.0 |
94 |
80 |
The above ratings are based on cable in Free air, in an ambient air temperature of 30°C.
For ambient air temperatures other than 30°C the following rating factors should be applied:
Ratings for cables up to and including 4mm2 are based on 60°C conductor operating temperature with 6mm2 and above based on 70°C operating temperature.
Correction Factors
Cables Up To and Including 4mm2 . Assuming 60°C Conductor Temperature
Ambient Temperature |
35°C |
40°C |
45°C |
50°C |
55°C |
Correction Factor |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |
Cables 6mm2 and above. Assuming 70°C Conductor Temperature
Ambient Temperature |
35°C |
40°C |
45°C |
50°C |
55°C |
60°C |
Correction Factor |
0.91 |
0.82 |
0.71 |
0.58 |
0.41 |
0.50 |
0.5 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
2 X 0.5 |
5.5 |
46 |
3 X 0.5 |
5.8 |
55 |
4 X 0.5 |
6.4 |
66 |
5 X 0.5 |
7.2 |
78 |
7 X 0.5 |
8.2 |
95 |
12 X 0.5 |
10.0 |
155 |
18 X 0.5 |
11.7 |
230 |
25 X 0.5 |
13.8 |
320 |
0.75 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
2 X 0.75 |
6.3 |
55 |
3 X 0.75 |
7.0 |
67 |
4 X 0.75 |
7.2 |
80 |
5 X 0.75 |
8.0 |
100 |
7 X 0.75 |
9.0 |
130 |
12 X 0.75 |
11.5 |
210 |
18 X 0.75 |
13.0 |
260 |
25 X 0.75 |
16.0 |
430 |
34 X 0.75 |
17.5 |
515 |
42 X 0.75 |
19.0 |
600 |
1.0 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
2 X 1.0 |
7.0 |
66 |
3 X 1.0 |
7.3 |
80 |
4 X 1.0 |
8.0 |
100 |
5 X 1.0 |
8.5 |
125 |
7 X 1.0 |
9.2 |
160 |
12 X 1.0 |
12.5 |
260 |
18 X 1.0 |
14.5 |
375 |
34 X 1.0 |
20.0 |
650 |
42 X 1.0 |
21.5 |
740 |
1.5 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
2 X 1.5 |
7.5 |
85 |
3 X 1.5 |
8.3 |
115 |
4 X 1.5 |
8.7 |
150 |
5 X 1.5 |
9.5 |
168 |
7 X 1.5 |
10.8 |
210 |
12 X 1.5 |
13.5 |
365 |
18 X 1.5 |
16.5 |
525 |
25 X 1.5 |
19.8 |
765 |
34 X 1.5 |
22.0 |
940 |
42 X 1.5 |
23.8 |
1050 |
2.5 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
2 X 2.5 |
9.5 |
130 |
3 X 2.5 |
10.5 |
170 |
4 X 2.5 |
11.4 |
210 |
5 X 2.5 |
12.5 |
260 |
7 X 2.5 |
14.0 |
345 |
4.0 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
3 X 4.0 |
10.6 |
265 |
4 X 4.0 |
11.5 |
350 |
5 X 4.0 |
12.7 |
480 |
7 X 4.0 |
14.0 |
6.0 mm2 conductor CY control cable
CORES & SIZE mm2 |
O/A |
WEIGHT |
4 X 6.0 |
15.5 |
550 |
5 X 6.0 |
15.7 |
|
7 X 6.0 |
16.6 |