Power Cables 

Power Cables

3800/6600VFour Core, XLPE Insulated, PVC Sheathed, Armoured to BS 6622

Voltage Rating :3800/6600V
Construction
Conductor :
Plain annealed stranded copper conductor
Insulation :
XLPE Compound
Copper tape Screen:
Copper tape Screen
Filler (where applicable) :Polypropylene yarn
Inner Jacket:PVC jacket
Armouring (for armoured cable) :Aluminium wire (single core) or Galvanized steel wires (multicore)
Separator Tape:Galvanized Steel Tape
Sheath :PVC/LSOH compound
Colour of identification :
Natural
Sheath Colour :
Black, Grey or White

Conductor Nominal Cross-sectional Area(mm2)

Insulation Thickness (mm)

Nominal Diameter over insulation(mm)

Nominal area of copper tape screen per core(mm2)

Nominal Thickness of PVC inner jacket(mm)

Nominal number and diameter of armour wires (No./mm)

Nominal thickness of PVC oversheath(mm)

Nominal overall diameter
(mm)

Approx. cable weight kg/km

25

2.5

13.1

3.5

1.3

49/2.0

2.5

43.9

3860

35

2.5

14.2

3.6

1.4

52/2.0

2.5

46.2

4637

50

2.6

15.5

4

1.5

46/2.5

2.8

50.8

5250

70

2.6

17

4.3

1.5

49/2.5

2.8

55

6352

95

2.6

18.9

4.8

1.6

54/2.5

3

59.5

7790

120

2.6

20.2

5.1

1.6

57/2.5

3

64

9120

150

2.7

21.8

5.5

1.7

60/2.5

3.2

66.9

10528

185

2.7

23.8

5.8

1.7

65/2.5

3.2

70.5

12371

240

2.7

26

6.5

1.8

71/2.5

3.5

76.6

14910

300

2.8

28.9

7.2

2

62/3.15

3.7

84.6

17348

400

3

32

8

2

69/3.15

3.9

92

21050