Power Cables 

Power Cables

3800/6600VThree Core, XLPE Insulated, PVC Sheathed, Armoured to BS 6622

Voltage Rating :3800/6600V
Construction
Conductor :
Plain annealed stranded copper conductor
Insulation :
XLPE Compound
Copper tape Screen:
Copper tape Screen
Filler (where applicable) :Polypropylene yarn
Inner Jacket:PVC jacket
Armouring (for armoured cable) :Aluminium wire (single core) or Galvanized steel wires (multicore)
Separator Tape:Galvanized Steel Tape
Sheath :PVC/LSOH compound
Colour of identification : Natural
Sheath Colour : Black, Grey or White

Conductor Nominal Cross-sectional Area(mm2)

Insulation Thickness (mm)

Nominal Diameter over insulation(mm)

Nominal area of copper tape screen per core(mm2)

Nominal Thickness of PVC inner jacket(mm)

Nominal number and diameter of armour wires (No./mm)

Nominal thickness of PVC oversheath(mm)

Nominal overall diameter
(mm)

Approx. cable weight kg/km

25

2.5

12.9

3.4

1.2

49/2.0

2.2

42

29.2

35

2.5

13.9

3.6

1.2

52/2.0

2.3

44.4

3486

50

2.5

15.2

3.9

1.3

46/2.5

2.5

48.8

4088

70

2.5

16.8

4.3

1.3

49/2.5

2.6

52.4

4914

95

2.5

18.5

4.7

1.4

54/2.5

2.7

56.5

5950

120

2.5

20

5

1.5

57/2.5

2.8

60.1

6959

150

2.5

21.3

5.3

1.5

60/2.5

2.9

63.1

7983

185

2.5

23.1

5.8

1.6

65/2.5

3

67.4

9628

240

2.6

25.5

6.3

1.7

71/2.5

3.2

73.2

11342

300

2.8

28.3

7

1.8

62/3.15

3.5

81.3

13651

400

3

31.4

7.7

2

69/3.15

3.7

88.8

16801