Power Cables | ||||||||||||||
Power Cables
BS 6622 Single Core Unarmoured ( Copper Wire Screen) 33KV XLPE Stranded Copper Conductors
Construction
cross-sectional area mmsq |
Minimum average thickness of insulation mm |
Nominal diameter over insulation
|
Nominal area of copper wire screen |
Nominal average thickness of PVC oversheath |
Nominal overall diameter of cable mm |
50 |
8 |
27.1 |
16 |
2.0 |
34.5 |
70 |
8 |
28.9 |
16 |
2.0 |
36.5 |
95 |
8 |
30.6 |
16 |
2.1 |
38.4 |
120 |
8 |
32.1 |
16 |
2.1 |
39.9 |
150 |
8 |
33.4 |
16 |
2.2 |
41.2 |
185 |
8 |
35.2 |
16 |
2.2 |
13.2 |
240 |
8 |
37.4 |
25 |
2.3 |
15.7 |
300 |
8 |
39.7 |
25 |
2.4 |
18.2 |
400 |
8 |
42.4 |
35 |
2.5 |
51.1 |
500 |
8 |
45.3 |
35 |
2.6 |
54.0 |
630 |
8 |
48.7 |
35 |
2.7 |
57.8 |
800 |
Please refer to our technical department for further information |
||||
1000 |
Installation
cross-sectional area mmsq |
Approximate cable weight kg/m |
Nominal drum length |
Minimum bending radius mm |
Nominal internal diameter of ducts mm |
50 |
1.5 |
1000 |
750 |
100 |
70 |
1.8 |
500 |
800 |
100 |
95 |
2.1 |
500 |
850 |
100 |
120 |
2.4 |
500 |
850 |
100 |
150 |
2.7 |
500 |
900 |
100 |
185 |
3.1 |
500 |
950 |
100 |
240 |
3.8 |
500 |
1000 |
100 |
300 |
4.5 |
500 |
1050 |
100 |
400 |
5.5 |
250 |
1100 |
100 |
500 |
6.6 |
250 |
1150 |
100 |
630 |
8.0 |
250 |
1250 |
100 |
800 |
Please refer to our technical department for further information |
|||
1000 |
Electrical Performance
cross-sectional area mmsq |
Maximum DC resistance of conductor at 20 ℃ uohms/m |
Maximum AC resistance of conductor at 90 ℃ uohms/m |
Reactance at 50Hz |
Impedance at 50Hz uohms/m |
Maximum Capacitace PF/m |
Maximum charging current at normal voltage and frequency mA/m |
50 |
387 |
494 |
152 |
516 |
138 |
0.83 |
70 |
268 |
343 |
143 |
371 |
154 |
0.92 |
95 |
193 |
248 |
135 |
281 |
169 |
1.01 |
120 |
153 |
196 |
130 |
235 |
183 |
1.10 |
150 |
124 |
159 |
126 |
202 |
194 |
1.16 |
185 |
99.1 |
128 |
122 |
176 |
210 |
1.26 |
240 |
75.4 |
98 |
117 |
152 |
229 |
1.37 |
300 |
60.1 |
80 |
113 |
138 |
249 |
1.49 |
400 |
47.0 |
64 |
109 |
126 |
273 |
1.64 |
500 |
36.6 |
51 |
105 |
116 |
298 |
1.79 |
630 |
28.3 |
42 |
102 |
110 |
327 |
1.96 |
800 |
Please refer to our technical department for further information |
|||||
1000 |
Ratings
Cross-sectional area |
Current Ratings |
Short circuit ratings |
|||
Laid in ground |
Drawn into ducts |
Laid in air |
One second short circuit rating of conductor |
One second short circuit rating of copper per core |
|
50 |
220 |
225 |
260 |
6.8 |
2.6 |
70 |
270 |
270 |
320 |
9.8 |
2.6 |
95 |
320 |
320 |
390 |
13.3 |
2.6 |
120 |
360 |
360 |
445 |
17.2 |
2.6 |
150 |
410 |
405 |
510 |
21.2 |
2.6 |
185 |
460 |
445 |
580 |
26.6 |
2.6 |
240 |
530 |
520 |
680 |
34.9 |
4.3 |
300 |
600 |
570 |
770 |
43.8 |
4.3 |
400 |
690 |
630 |
890 |
57.3 |
5.8 |
500 |
760 |
700 |
1020 |
72.3 |
6.0 |
630 |
850 |
780 |
1160 |
91.2 |
5.8 |
800 |
Please refer to our technical department for further information |
||||
1000 |