450/750V sR Insulated control cables (2-5 cores)
FFX200 07SZ1-R (PH60) (CU/SR/LSZH 450/750V Class 2)
APPLICATION
The cables are designed, manufactured and tested for general application in power supply and
signal wiring, for emergency circuit and fire circuit control.
STANDARDS
Basic design to BS 7629-1
FIRE PERFORMANCE
Circuit Integrity |
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180);
BS 8434-1 (30mins); BS 5839-1 Clause 26 2d; CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3(CR1) |
Circuit Integrity with mechanical shock |
EN 50200(PH60); CEI 20-36/4-0 |
Circuit Integrity with mechanical shock & water spray |
EN 50200 annex E |
System circuit integrity |
DIN 4102-12, E30 depending on lay system |
Flame Retardance (Single Vertical
Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2;
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test) |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
450/750 V
CABLE CONSTRUCTION
Conductors: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Fire resistant silicone rubber compound type EI2 as per BS 7655-1.1.
Cabling: The cores are cabled together in concentric layers with suitable non-hygroscopic fillers.
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH
compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation Colour:
Without earth conductor
2 cores blue - brown
3 cores brown - black - grey
4 cores blue - brown - black - grey
5 cores blue - brown - black - grey - black
With earth conductor
3 cores yellow/green - blue - brown
4 cores yellow/green - brown - black - grey
5 cores yellow/green - blue - brown - black - grey
Sheath Colour: Colour red (other colours on request)
Physical AND THERMAL PROPERTIES
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 7.5 x Overall Diameter
Electrical PROPERTIES
Dielectric test: |
2500 V r.m.s. x 5' (core/core) |
Insulation resistance |
≥300 MΩ x km (at 20°C) |
Short circuit temperature |
350°C |
CONSTRUCTION PARAMETERS
Cable Code |
No. of Core X Cross Section |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Approx.
Weight |
|
mm2 |
mm |
mm |
mm |
kg/km |
2 core, |
FFX200 07SZ1-R (PH60) |
2x1.5 |
0.8 |
1.0 |
7,8 |
96 |
FFX200 07SZ1-R (PH60) |
2x2.5 |
0.9 |
1.1 |
9,2 |
138 |
FFX200 07SZ1-R (PH60) |
2x4.0 |
0.9 |
1.2 |
10,5 |
189 |
3 core |
FFX200 07SZ1-R (PH60) |
3x1.5 |
0.8 |
1.0 |
8,3 |
116 |
FFX200 07SZ1-R (PH60) |
3x2.5 |
0.9 |
1.1 |
9,8 |
169 |
FFX200 07SZ1-R (PH60) |
3x4.0 |
0.9 |
1.2 |
11,6 |
246 |
4 core |
FFX200 07SZ1-R (PH60) |
4x1.5 |
0.8 |
1.1 |
9,3 |
147 |
FFX200 07SZ1-R (PH60) |
4x2.5 |
0.9 |
1.2 |
11,3 |
222 |
FFX200 07SZ1-R (PH60) |
4x4.0 |
0.9 |
1.3 |
12,5 |
299 |
5 core |
FFX200 07SZ1-R (PH60) |
5x1.5 |
0.8 |
1.1 |
10,5 |
180 |
FFX200 07SZ1-R (PH60) |
5x2.5 |
0.9 |
1.2 |
12,3 |
259 |
FFX200 07SZ1-R (PH60) |
5x4.0 |
0.9 |
1.3 |
14,0 |
359 |
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Nominal
Cross
Section
Area |
Reference
Method 4
(enclosed in
an conduit
insulated wall
etc) |
Reference Method 3
(enclosed in conduit on
a wall or ceiling, or in
trunking) |
Reference Method 1
(clipped direct) |
Reference Method 11
(on a perforated cable
tray), or Reference Method |
one 3-core
cable or one
4-core cable
3-phase a.c. |
one 2-core
cable
single phase
a.c. or d.c. |
one 3-core
cable or one
4-core cable
3-phase a.c. |
one 2-core
cable
singlephase
a.c. or d.c. |
one 3-core
cable or one
4-core cable
3-phase a.c. |
one 2-core
cable
singlephase
a.c. or
d.c. |
one 3-core
cable or one
4-core cable
3-phase a.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
1.5 |
16.5 |
22 |
19.5 |
24 |
22 |
26 |
23 |
2.5 |
22 |
30 |
26 |
33 |
30 |
36 |
32 |
4 |
30 |
40 |
35 |
45 |
40 |
49 |
42 |
Voltage Drop (Per Amp Per Meter)
Nominal Cross
Section Area |
2-core cable d.c. |
2-core cable single- phase a.c |
3-core or 4-core cable
3-phase a.c. |
1 |
2 |
3 |
4 |
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
1.5 |
31 |
31 |
27 |
2.5 |
19 |
19 |
16 |
4 |
12 |
12 |
10 |
|